ANALYSIS OF ELECTRICAL TESTS ON A 300 kVA TRANSFORMER: PARAMETER EVALUATION AND DIAGNOSIS
Abstract
This article analyzes electrical test results obtained from a 300 kVA three-phase transformer, with a 15 kV voltage class, to assess parameters related to the windings, insulation system, and magnetic core. The study combines a literature review with a descriptive analysis of experimental records covering transformer turns ratio, winding resistance, insulation resistance, no-load losses, load losses, short-circuit impedance, and dielectric tests. Across three phases and five tap-changer positions, the largest turns-ratio deviation was −0.118%, within the ±0.5% tolerance adopted for the analysis. Recorded values included 501 W of no-load losses, 0.62% excitation current, and 4.48% short-circuit impedance. Insulation resistance measurements were 83.7 GΩ between high- and low-voltage windings, 53.8 GΩ between high voltage and ground, and 42.7 GΩ between low voltage and ground. These results characterize the transformer's behavior under the tested conditions. A definitive compliance assessment for each parameter still requires the applicable technical limits and test conditions to be explicitly documented. The analysis highlights the importance of measurement traceability and the joint interpretation of different tests.
Author Biographies
Universidade de Araraquara (UNIARA). Undergraduate student in Electrical Engineering at the Universidade de Araraquara (UNIARA).
Universidade de Araraquara (UNIARA). Associação São Bento de Ensino, CPFL Energia, Cervejarias Kaiser Brasil Ltda, Empresa Paulista de Embalagens Agroindustriais - EPEMA, National Service for Industrial Training São Paulo (SENAI-SP), Tetra Pak Ltda, UNIARA, Universidade Cândido Mendes, Department of Mathematics of the Federal University of São Carlos.
References
[1] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 5356-1:2025: Transformadores de potência — Parte 1: Generalidades. Rio de Janeiro: ABNT, 2025.
[2] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 5356-3:2007: Transformadores de potência — Parte 3: Níveis de isolamento, ensaios dielétricos e espaçamentos externos em ar. Versão corrigida 2, 2014. Rio de Janeiro: ABNT, 2014.
[3] HEATHCOTE, Martin J. J & P Transformer Book. 13. ed. Oxford: Newnes, 2007. DOI: https://doi.org/10.1016/B978-075068164-3/50003-X
[4] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 5440:2014: Transformadores para redes aéreas de distribuição — Requisitos. Versão corrigida de 2014. Rio de Janeiro: ABNT, 2014.
[5] CHAPMAN, Stephen J. Fundamentos de máquinas elétricas. 5. ed. Porto Alegre: Bookman, 2013.
[6] VICENTE, José Manuel Esteves. Uma contribuição à automação de ensaios em transformadores de potência em média tensão. 2006. 162 f. Tese (Doutorado em Engenharia Elétrica) – Universidade Federal de Itajubá, Itajubá, 2006.
[7] INTERNATIONAL ELECTROTECHNICAL COMMISSION. IEC 60076-1:2011: Power transformers — Part 1: General. 3. ed. Geneva: IEC, 2011.
[8] INTERNATIONAL ELECTROTECHNICAL COMMISSION. IEC 60076-3:2013+AMD1:2018: Power transformers — Part 3: Insulation levels, dielectric tests and external clearances in air. Consolidated version. Geneva: IEC, 2018.
[9] CELESC DISTRIBUIÇÃO S.A. E-313.0019: Transformadores para redes aéreas de distribuição. Revisão de março de 2025. Florianópolis: Celesc Distribuição, 2025. Disponível em: https://www.celesc.com.br/arquivos/normas-tecnicas/especificacao-tecnica/E3130019.pdf Acesso em: 14 nov. 2026.